Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 15 of 36
Procedure Steps Display
Change the
override
setpoint
Entering an override setpoint can only take place if the EZstat is in the
unoccupied mode.
1. Push the buon under the unoccupied icon .
2. Press either the or buon to change the rst digit of the
password.
3. Press the Enter buon to select the next digit. Repeat for all four
digits.
4. Press either the or buon to turn the override on or o.
Override O—The controller uses the unoccupied setpoint as the acve
setpoint.
Override On—the controller changes to the occupied setpoint
which can then be temporarily changed.
5. Press the Enter buon to save the seng.
When the system is in the unoccupied mode, changing the acve setpoint will
automacally place the system in the override mode.
F
°
65
AUTO AUTO
Enter
Cncl
LOCAL OVRD: ON
OFF
Change the
display units
To temporarily change the display units to either Celsius or Fahrenheit,
press and hold the middle buon under the display unl the units change.
F
°
70
AUTO AUTO
°
21
C
.0
AUTO AUTO
NOTE
6 COMMISSIONING FUNCTIONS
The topics in this secon are advanced topics for control technicians and engineers. These topics cover procedures for the inial
EZstat setup.
The EZstat commissioning funcons are values and sengs that are entered during the installaon and commissioning of a
controller and the equipment it is controlling. Typically these funcons do not change aer the installaon and commissioning
process.
To set up the commissioning funcons, you will need the following informaon:
Informaon about the equipment
The sequence of operaon for the equipment
The building automaon system plans for controllers that are part of a network.
Users may change the occupied heang and cooling setpoints without accessing the commissioning funcons. This procedure
is covered in the topic User funcons.